Part No. : TJK436400WL | Manufacturer : General Electric Co | CAGE Code : 60969 |
Item Name : Circuit Breaker | FSC : 5925 Circuit Breakers | NSN : 5925-01-044-2306 |
You can send a request for quote for p/n TJK436400WL to ASAP Semiconductor using justpartsunlimited.com. This part is manufactured by General Electric Co (CAGE Code 60969). The description of it is Circuit Breaker. The national stock number associated with this part is NSN 5925010442306. This part belongs to FSC Circuit Breakers part family. An associate from ASAP Semiconductor will respond within 15 minutes to your query. It is our pleasure to help you with TJK436400WL part requirements.
Required fields compulsory *
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-044-2306 Item Description: Circuit Breaker | 5925 | 010442306 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Tjk436400wl | 5 | 1 | C | A |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 10.125 INCHES NOMINAL |
ADAT | BODY WIDTH | 8.240 INCHES MINIMUM AND 8.250 INCHES MAXIMUM |
ADAU | BODY HEIGHT | 3.812 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 7.750 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 2.750 INCHES NOMINAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.190 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 7.750 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 2.750 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.187 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
APNQ | ARC QUENCHING METHOD | AIR |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CBBL | FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
CBME | III CUBIC MEASURE | 465.093 CUBIC INCHES |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 400.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 22000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CPSF | ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +1200.0 TO 4000.0 AC ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
FEAT | SPECIAL FEATURES | TWO LINE SHIELDS TO BE INCLUDED WITH EACH BREAKER |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
Please contact us to receive an instant quotation