Part No. : SM33-15-250VAC60C1 | Alternate P/N : SM3315250VAC60C1 | Manufacturer : Eaton Corporation |
CAGE Code : 74193 | Item Name : Circuit Breaker | FSC : 5925 Circuit Breakers |
NSN : 5925-00-626-4343 |
You can send a request for quote for p/n SM33-15-250VAC60C1 to ASAP Semiconductor using justpartsunlimited.com. This part is manufactured by Eaton Corporation (CAGE Code 74193). The description of it is Circuit Breaker. The national stock number associated with this part is NSN 5925006264343. This part belongs to FSC Circuit Breakers part family. An associate from ASAP Semiconductor will respond within 15 minutes to your query. It is our pleasure to help you with SM33-15-250VAC60C1 part requirements.
Required fields compulsory *
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-626-4343 Item Description: Circuit Breaker | 5925 | 006264343 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | 0 | ||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Sm33-15-250vac60c1 | E | 1 | C |
MRC | Criteria | Characteristic |
---|---|---|
AAJE | THREAD PITCH DIAMETERS | +0.3503/+0.3537 INCHES |
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ABXD | BUSHING LENGTH | 0.380 INCHES MAXIMUM |
ADAQ | BODY LENGTH | 1.562 INCHES MAXIMUM |
ADAT | BODY WIDTH | 1.281 INCHES MAXIMUM |
ADTV | CASE MATERIAL | METAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.906 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.625 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.828 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 2 |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 300.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 ALL LOCATIONS |
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 3.000 MINIMUM ALL LOCATIONS AND 60.000 MAXIMUM ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQJX | NOMINAL THREAD SIZE | 0.375 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.500 MINIMUM AT 200 PCT ALL LOCATIONS AND 9.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND HERMETICALLY SEALED |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TEST | TEST DATA DOCUMENT | 81349-MIL-C-39019 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTI |
THSD | THREAD SERIES DESIGNATOR | UNEF |
TTQY | TERMINAL TYPE AND QUANTITY | 4 WIRE HOOK |
ZZZK | SPECIFICATION/STANDARD DATA | 81349-MIL-C-39019/3 GOVERNMENT SPECIFICATION |
Please contact us to receive an instant quotation