Part No. : AKR-7B-30 | Alternate P/N : AKR7B30 | Manufacturer : General Electric Co |
CAGE Code : 60969 | Item Name : Circuit Breaker | FSC : 5925 Circuit Breakers |
NSN : 5925-01-120-0886 |
You can send a request for quote for p/n AKR-7B-30 to ASAP Semiconductor using justpartsunlimited.com. This part is manufactured by General Electric Co (CAGE Code 60969). The description of it is Circuit Breaker. The national stock number associated with this part is NSN 5925011200886. This part belongs to FSC Circuit Breakers part family. An associate from ASAP Semiconductor will respond within 15 minutes to your query. It is our pleasure to help you with AKR-7B-30 part requirements.
Required fields compulsory *
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-120-0886 Item Description: Circuit Breaker | 5925 | 011200886 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Akr-7b-30 | 5 | 2 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
ABHP | OVERALL LENGTH | 27.000 INCHES NOMINAL |
ABKW | OVERALL HEIGHT | 22.250 INCHES NOMINAL |
ABMK | OVERALL WIDTH | 20.380 INCHES NOMINAL |
ADTV | CASE MATERIAL | METAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.690 INCHES NOMINAL |
AGAV | END ITEM IDENTIFICATION | S/S SWITCHBOARD ABOARD 140 FT WTGB CLASS COAST GUARD VESSELS |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 400.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 440.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 42000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | SOLID STATE ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | ELECTRIC |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CQTL | RESET ACTUATOR VOLTAGE RATING AND TYPE IN VOLTS | 120.0 AC |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 22.000 MAXIMUM AT 125 PCT ALL LOCATIONS |
FEAT | SPECIAL FEATURES | CIRCUIT BREAKER IS A DRAWOUT TYPE EQUIPPED WITH LONG AND SHORT TIME INSTANTANEOUS TRIP; 120VAC SHUNT TRIP W/REMOTE RELEASE; 6 STAGE AUX SWITCHES W/6NO-6NC CONTACTS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 BUS BAR |