Part No. : G613002-1 | Alternate P/N : G6130021 | Manufacturer : Lucent Technologies Inc |
CAGE Code : 01714 | Item Name : Circuit Breaker | FSC : 5925 Circuit Breakers |
NSN : 5925-00-513-2844 |
You can send a request for quote for p/n G613002-1 to ASAP Semiconductor using justpartsunlimited.com. This part is manufactured by Lucent Technologies Inc (CAGE Code 01714). The description of it is Circuit Breaker. The national stock number associated with this part is NSN 5925005132844. This part belongs to FSC Circuit Breakers part family. An associate from ASAP Semiconductor will respond within 15 minutes to your query. It is our pleasure to help you with G613002-1 part requirements.
Required fields compulsory *
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-513-2844 Item Description: Circuit Breaker | 5925 | 005132844 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
G613002-1 | 2 | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM |
ADAT | BODY WIDTH | 2.990 INCHES MINIMUM AND 3.010 INCHES MAXIMUM |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM |
AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 4 |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 300.0 MILLIAMPERES DC FOURTH LOCATION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC FIRST LOCATION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC SECOND LOCATION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC THIRD LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC FIRST LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SECOND LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC THIRD LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 50.0 DC FOURTH LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC FIRST LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SECOND LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC THIRD LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 DC FOURTH LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 4 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, THREE, AND FOUR LINKED |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 3 ALARM |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | RELAY TRIP FOURTH LOCATION |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATION |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SECOND LOCATION |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP THIRD LOCATION |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE AND INTERNAL AT POLE TWO AND INTERNAL AT POLE THREE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.500 MINIMUM AT 200 PCT ALL LOCATIONS AND 7.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | MOISTURE RESISTANT AND FUNGUS RESISTANT |
CRTK | SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 2.5 AC AND 1.0 DC |
CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC AND 50.0 DC |
FREQ | FREQUENCY IN HERTZ | 60.0 FIRST LOCATION |
FREQ | FREQUENCY IN HERTZ | 60.0 SECOND LOCATION |
FREQ | FREQUENCY IN HERTZ | 60.0 THIRD LOCATION |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 8 THREADED STUD |
Please contact us to receive an instant quotation