Part No. : HM2-224-012 | Alternate P/N : HM2224012 | Manufacturer : Eaton Corporation |
CAGE Code : 74193 | Item Name : Circuit Breaker | FSC : 5925 Circuit Breakers |
NSN : 5925-01-396-1121 |
You can send a request for quote for p/n HM2-224-012 to ASAP Semiconductor using justpartsunlimited.com. This part is manufactured by Eaton Corporation (CAGE Code 74193). The description of it is Circuit Breaker. The national stock number associated with this part is NSN 5925013961121. This part belongs to FSC Circuit Breakers part family. An associate from ASAP Semiconductor will respond within 15 minutes to your query. It is our pleasure to help you with HM2-224-012 part requirements.
Required fields compulsory *
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-396-1121 Item Description: Circuit Breaker | 5925 | 013961121 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Hm2-224-012 | 5 | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AKPX | Pole Quantity | 2 |
CPLM | Maximum Continuous Load Current Rating Per Pole | 1.0 AMPERES AC ALL LOCATIONS AND 1.0 AMPERES DC ALL LOCATIONS |
ABXD | Bushing Length | 0.380 INCHES MAXIMUM |
AJWX | Mounting Surface To Terminal End Distance | 1.780 INCHES NOMINAL |
FREQ | Frequency In Hertz | 400.0 ALL LOCATIONS |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 240.0 AC ALL LOCATIONS AND 50.0 DC ALL LOCATIONS |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
CQSM | Switch Location And Position Designation | INTERNAL AT POLE ONE |
CPRJ | Trip Release Method | MAGNETIC ALL LOCATIONS |
AXHR | Mounting Facility Type And Quantity | 1 THREADED BUSHING W/PANEL SEAL |
AEGJ | Switch Contact Arrangement | SINGLE POLE, DOUBLE THROW |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 125.0 ALL LOCATIONS |
CPRL | Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CSSX | Switch Current Rating And Type In Amps | 0.5 AC AND 0.5 DC |
ADAT | Body Width | 1.281 INCHES MAXIMUM |
CPRX | Actuator Position Designation | BETWEEN POLE ONE AND TWO |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
CPSM | Internal Trip Release Configuration | SERIES TRIP ALL LOCATIONS |
ADTV | Case Material | PLASTIC |
CPRW | Actuator Function | TRIP-RESET |
CSWP | Switch Voltage Rating And Type In Volts | 120.0 AC AND 50.0 DC |
CRTK | Switch Terminal Type | TAB, SOLDER LUG |
THSD | Thread Series Designator | UNEF |
CQJX | Nominal Thread Size | 0.375 INCHES |
ADAQ | Body Length | 1.562 INCHES MAXIMUM |
AEBP | Center To Center Distance Between Terminals Parallel To Length | 0.875 INCHES NOMINAL |
TTQY | Terminal Type And Quantity | 4 WIRE HOOK |
AAQL | Body Style | MULTIPOLE-SINGLE ACTUATOR TYPE |
AEBQ | Center To Center Distance Between Terminals Parallel To Width | 0.625 INCHES NOMINAL |
MRC | Decoded Requirement | Clear Text Reply |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 300.0 AC ALL LOCATIONS AND 500.0 DC ALL LOCATIONS |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 0.500 MINIMUM AT 200 PCT ALL LOCATIONS AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CPRQ | Reset Method | MANUAL |
CPRZ | Auxiliary Switch Function And Quantity | 1 ALARM |
Please contact us to receive an instant quotation